fanairnew.jpg (75950 bytes)FanAir Company

Panel Venturi Fans.                                                                    

Designed for Air Circulation, Air Supply or Exhaust applications.

2 to 3 day 'Quick Shipment' on sizes up to 48" Dia is available.


Belt Drive and Direct Drive Panel Fans

shutters.jpg (15129 bytes)

Sizes and Capacity:
From 12" to 144" Diameter.
800 CFM to 144,000 CFM
 

Description:
Rugged Heavy Duty constructed Panel Fans designed to move a large volume of air within a minimum of space. Panel Venturi propellers utilize the latest improvements in adjustable pitch design. The blades and hubs are separate castings accurately machined, matched and balanced. All propellers are cast of a special aluminum alloy of high tensile strength. Propellers with fixed pitch are furnished on standard units where capacity requirements are known.

Applications:
Air exhaust, Air supply, Recirculation Air, Engine Room Air Exchange, Shop Ventilation, Plant Ventilation, Garage Ventilation, Enclosure Ventilation, Portable Air Cooling.
Product Features / Options:
  • All steel or aluminum construction.
  • Airfoil Impellers.
  • Belt or Direct Drive.
  • Continuous duty rated.
  • Wall Collars.
  • Safety Screens.
  • Filter Racks with Filters.
  • Gravity or Motorized Shutters
  • Supply or Exhaust Configuration.
  • Quiet and Efficient.
  • Ships fully assembled.
  • Special Coatings, Stainless Steel or Aluminum construction is available.
   

 

 


Panel Venturi Sample Specifications

GENERAL 1.0

  1. Fans shall be tested and rated in accordance with AMCA air and sound methods and standards.
  2. Fans shall conform to AMCA 99 Standards.
  3. All motors and electrical components shall comply to NEMA, UL or other governing body.

PRODUCT 2.0

  1. Fan shall be of an axial flow propeller, panel fan mount, direct driven configuration.
  2. Fan panel assembly shall be of all welded construction, and shall be constructed completely of carbon steel, aluminum or stainless steel as indicated on the fan schedule. The fan panel shall have an integrally die formed, deep shroud for smooth air entry into the propeller.
  3. The fan's motor support consist of a rigid steel formed structure welded directly to the fan panel.
  4. The propeller shall be constructed of cast aluminum blades fastened directly to a cast aluminum hub assembly. The hub is designed to incorporate a taper lock bushing and keyed directly to the motor shaft. Fan mounting panel assembly shall be coated with enamel as standard or optional other available coating as made available by coating suppliers and as indicated on the fan schedule. The propeller is uncoated.
  5. The final complete fan assembly is vibration tested and balanced as per AMCA 204, grade BV-3.
  6. The motor shall be of a typical NEMA -T frame type and typical with the motor industry. The electric motor shall be as indicated on the fan schedule and as available from the motor vendors

 PRINCIPALS AND FUNCTION 3.0

  1. Fan performance rating shall be based on methods as developed by AMCA standard 210.
  2. Form, function and application of the fan shall be as defined by ASHRAE, AMCA and SMACNA in regard to air system design in compatibility with the fan.

ACCESSORIES 4.0

  1. The fan shall have front and or rear safety guards as indicated on the fan schedule.
  2. The fan shall have be of a fixed, reversed air flow configuration with a double entry bell on the fan panel as indicated on the fan schedule.
  3. The fan shall have be of a reversible air flow configuration for supply or exhaust with a double entry bell on the fan panel as indicated on the fan schedule.